Direct answer: For evaporative (wet) cooling towers, site altitude mainly changes air density and fan/motor conditions—not a simple “cut capacity X%” rule you can invent from a catalog page. Enter the project elevation (or barometric pressure) in the manufacturer selection, and treat dry or adiabatic coolers differently from wet towers. Do not paste a sea-level model number onto a high-elevation site without a factory re-selection.
THERMIVON is the overseas brand of Jiangxi Zhaorin Heat Transfer Technology Co., Ltd. This article is a buyer checklist for overseas RFQs. It does not replace a project-specific thermal selection.
What actually changes at altitude
- Air density falls as barometric pressure falls. Fans still move roughly the same volume at a fixed speed, but mass flow drops.
- Evaporative (wet) towers reject heat primarily toward the entering wet-bulb temperature. Industry manufacturer guidance states evaporative capacity is not simply derated the same way as dry coolers when altitude rises; lower barometric pressure can aid evaporation. Still, the selection must use the real site wet-bulb and pressure/altitude inputs.
- Dry and adiabatic coolers reject heat toward dry-bulb / process air-side duty. Lower air mass flow typically reduces capacity at altitude unless the selection accounts for it.
- Motors: Many motor standards assume ratings near or below about 1,000 m. Above that elevation, cooling of the motor itself can be affected—confirm the motor supplier’s altitude rating instead of assuming a catalog nameplate is enough.
Public manufacturer reference used here: SPX Cooling / Marley expert opinion white paper on altitude effects for heat-rejection equipment (evaporative vs dry/adiabatic contrast, motor note): https://spxcooling.com/wp-content/uploads/WP-HR-251.pdf. Fan affinity / density relationship background is also discussed in SPX educational notes such as H-001B.
Where a generic altitude “percent derate” goes wrong
Buyers sometimes ask for a single percentage to shrink a sea-level catalog rating. That shortcut is unsafe because:
- Wet vs dry/adiabatic equipment respond differently.
- Approach, range, and design wet-bulb still dominate wet-tower thermal balance.
- Fan speed control, static pressure, and motor altitude class are separate from fill thermal rating.
- Published THERMIVON catalog ratings on the website are tied to stated sample conditions (including a stated atmospheric pressure on factory data sheets). If your site pressure differs materially, the model must be re-run—not verbally “guaranteed” equal.
RFQ information checklist (altitude projects)
- City / site elevation (m or ft) and/or design barometric pressure
- Design entering wet-bulb (and dry-bulb if dry/adiabatic is considered)
- Hot / cold water (or process fluid) temperatures and flow or heat load
- Open-circuit vs closed-circuit preference (process fluid isolation needs)
- Power supply, fan control (across-the-line / VFD), and any motor altitude class requirement
- Noise limit and measurement basis if applicable
Product paths on this site (start points, not substitutes for selection)
- Open-circuit FRP crossflow family example: SRN III FRP Crossflow
- Open-circuit FRP counterflow family example: SCT III FRP Counterflow
- Closed-circuit counterflow example: SCC Closed-Circuit
- Dry / adiabatic paths when water use is constrained: SDV V-Type Dry Cooler, SHA Adiabatic Dry Cooler
Related reading already on the blog: Open-Circuit vs Closed-Circuit Cooling Towers. For a formal quotation path: Get a Quote.
What we are not inventing here
This draft does not publish a proprietary THERMIVON altitude derate table, CTI letter numbers for a specific altitude project, or unnamed customer cases. Those require project data and factory confirmation.


